RE-2X(St)H-CI MC FE-180 PH120
Ref.Std. EN 50288-7 300 / 500 V
Multi-Core, Overall Screen, Fire Resistant Signalization Cables
Construction
Inner Conductor: Elc.stranded annealed copper wire (IEC 60228, class2)
Insulation: 2X  Mica tape on the XLPE insulation ( EN 50290-2-29)
Lay-Up: Cores are twisted in layers. Fixed with PES tape.
General Screen: (St)  %100 Coverage AL-PES tape ve 0,50 mm² (7x0,30 mm) screened with tinned strand drain wire.
Outer Sheath: H  HFFR sheath (EN 50290-2-27)
Sheath Color: RAL 9005 Black, RAL 5015 Blue or  RAL 7001 Gray

General Features
Flame Retardancy: IEC 60332-1,  EN 60332-1
Flame Retardent: IEC 60332-3-22 Cat A, EN 60332-3-22 Cat A, VDE 0482-332-3-22 Cat A
Halogen/Corrosive Gas Test: IEC 60754-2, EN 50267-2, VDE 0482-267-2
Smoke Density: IEC 61034-2, EN 61034-2, VDE 0482-1034-2
Insulation continuity test: EN 60331, VDE 0472 Part 814
Circuit Integreyty With Shock (PH): EN 50200, VDE 0482-200
Oil Resistance: ICEA S-82-552
Application
These cables are generally employed in instrumentation and control systems, analog and digital signal transmission of chemical and petrochemical industrial premises, power plants, natural gas and petroleum industries, etc.  Direct connection is not permitted under ambient with a low impedance sources.  They are suitable in dry and wet indoor and outdoor installations.