J-HH…Bd FE-180 PH120 |
|
Ref. Std. VDE 0815/TSE K 173 Fire Resistant, Internal Installation Communication and Fire Alarm Cables |
|
|
|
|
|
Construction |
|
Inner Conductor: Electrolytic mono annealed copper (EN 60228, class 1) Insulation:
Mica tape On HFFR insulation (EN 50290-2-26) Core colors will be
suitable to VDE 0815. Up to 4 pairs can produce different core
color combination. Lay-Up: Dual twisted cores are twisted together in 4-units, 4 units are twisted in layers and fixed with PES tape.(Figure 1) Flame Barrier: To increase the flame resistance of twisted cores, wrapped with special flame retardant glass fiber tape. Outer Sheath: HFFR (EN 50290-2-27, VDE0207 HM2) Sheath Color: RAL 2003, Orange |
|
General Features |
|
Flame Retardancy: IEC 60332-1, EN 60332-1, VDE 0482-332-1 Flame Spread: IEC 60332-3-24, EN 60332-3-24, VDE 0482-332-3-24 Halogen/Corrosive Gas Test: IEC 60754-2, EN 50267-2, VDE 0482-267-2 Smoke Density: IEC 61034-2, EN 61034-2, VDE 0482-1034-2 Insulation Continuity Test: EN 60331, VDE 0472 Part 814 Circuit Integrity With Shock: EN 50200, VDE 0482-200 |
|
Application |
|
These cables can function in case of fire Halgen Free, flame retardant, low smoke denstiy, Acidic (Corrosive) Gas Test, air ports, hospitals, metro, subway stations, shopping centers, high rise buildings, hotels, industrials plants and so on. signal and communication cables are used as an emergency circuits. |
|
Product Data-Sheet |
|
Click for product PDF file |